Products · Europe
Portable extinguishers filled with FW-18, the water-based agent for lithium-ion battery fires. The figures of the 6 L and 3 L models come from the technical file prepared for EN 3 testing. The models are not yet approved for sale in the EU.
Korea has its own line-up with stainless-steel bottles. See the Korean line-up

MS/AL6
Standard model. Also available as 6 L LT with the low-temperature agent, for unheated sites.

MS/AL3
Compact model with half the agent and half the discharge time of the 6 L.

Handheld unit. Its specifications are not fixed yet.
Sample images with the label layout under review. They do not show production units, and the sizes are approximate.
| Model | FW-18 6 LMS/AL6 | FW-18 6 L LTMS/AL6-LT (−20 °C) | FW-18 3 LMS/AL3 | FW-18 500 mL |
|---|---|---|---|---|
| Agent | FW-18 | FW-18 (LT-20) · freezing point < −25 °C | FW-18 | FW-18 |
| Charge | 6.0 L | 6.0 L | 3.0 L | 500 mL |
| Propellant | N₂ · 0.25 kg | N₂ · 0.25 kg | N₂ · 0.2 kg | To be confirmed |
| Charge pressure | 1.2–1.4 MPa at 20 °C | To be confirmed | 1.2–1.4 MPa at 20 °C | To be confirmed |
| Total mass | 9.75 kg | 9.75 kg† | 5.4 kg | To be confirmed |
| Discharge time | 90 s | 90 s† | 45 s | To be confirmed |
| Discharge range | 3–5 m | 3–5 m† | 3–4 m | To be confirmed |
| Operating temperature | +5 to +60 °C† | −20 to +60 °C† | +5 to +60 °C | To be confirmed |
| Declared rating | 13A · 600 Wh† | 13A · 600 Wh† | 8A · 600 Wh† | To be confirmed |
| Pressure gauge | 12 bar · green zone 9.5–14.5 bar | 12 bar · green zone 9.5–14.5 bar | 12 bar · green zone 9.5–14.5 bar | To be confirmed |
| Hose with nozzle | ≈ 520 mm | ≈ 520 mm | ≈ 475 mm | To be confirmed |
| Cylinder | Ø162 × 448 mm · steel | Ø162 × 448 mm · steel | Ø130 × 340 mm · steel | To be confirmed |
| Cylinder pressure | PS 18 bar · PT 27 bar · burst ≥ 49 bar | PS 18 bar · PT 27 bar · burst ≥ 49 bar | PS 18 bar · PT 27 bar · burst ≥ 49 bar | To be confirmed |
† Declared or proposed value from the technical file. The final value is the result of the EN 3-7 and EN 3-11 tests. The 600 Wh lithium-ion rating has not been tested yet.
Label
The label follows the five-part layout of EN 3-7. Shown here is the layout under review for the 6 L model.

FW-18 6 L with label
Red steel cylinder with hose, pressure gauge and base ring.

Label, 6 L
The rating, the statement about electrical equipment and the CE field are placeholders. The final wording depends on the EN 3-7 dielectric test and the EN 3-11 lithium-ion fire test.
Distributors receive the technical file and each approval document when it is issued.