01Fixed fire extinguishing system test: LFP pack
In-house comparison test, three agents under the same procedure. 시험 방법 참조: General technical requirements for fire prevention and control devices for lithium-ion power battery boxes of electric buses.
| Cells | CATL lithium iron phosphate (LiFePO₄ / graphite), 173 × 46 × 133 mm |
|---|---|
| Test pack | 3P4S: three cells in parallel per module, four modules in series |
| Preconditioning | Fully charged 48 h before the test; 3.6–3.65 V per cell verified |
| Instrumentation | 12 thermocouple channels (CH01–CH12) |
| Suppression | Water-mist system, constant 4 MPa, 240 s spray |
절차
- Keep the fully charged battery in an overcharged state.
- After 180 s, heat the battery with a heating plate for 780 s, then stop heating and overcharging and let thermal runaway develop.
- Activate the water-mist system: constant 4 MPa for 240 s.
- Observe the pack after extinguishing.
합격 기준
- The flame is completely extinguished and there is no re-ignition within 1 hour.
- After 1 hour, at least one unburned battery cell remains.
결과
| 약제 | 화염 소멸 | 재발화 | 소화 후 최고 온도 |
|---|---|---|---|
| Deionized water | 2 min | 있음 | > 400 °C |
| A mainstream Li-ion extinguishing agent | 1 min 20 s | 있음 | > 500 °C |
| FW-18 | 2 s | 없음 | < 100 °C |
- Cooling effect: FW-18 > a mainstream Li-ion extinguishing agent > deionized water.
- FW-18 terminated thermal runaway; with the other two agents the pack re-ignited.